| GN8020-E Point-Type Toxic gas detector |
|
| Click
on View [ Dimension
& Mounting / wiring terminal/The type of gas ] |
| |
| ■
Characteristic: |
| |
| ● |
0、1、2、4~20、22mA current/mod-bus signal output |
● |
2 cable entries convenient to install |
|
| ● |
4 digits high-light LED,Magnet Pen set |
● |
IIndependent gas chamber structure, and the sensor is easy to replace |
|
| ● |
Import sensor of high accuracy & anti-poisoning |
● |
Own intellectual property rights
with self-determination |
|
| ● |
Automatic zero-tracing, temperature compensating |
● |
Explosion Prevention Mark ExdⅡCT6 |
|
| ● |
2 Programmable Linkage Output Interface |
|
|
|
| |
| ■
Working theory: |
| |
GN8020-E Toxic gas detector first sample the signal from sensor,then deal the signal with the internal data processing, final output the consistence of ambient air by the signal such as 4~20mA , Mod-bus digital frame.
The GN8020-E can use in system with our company's GN90000-B、GN90000-P、GN90000-F、GN90000-A、GN90000-S gas controller. Otherwise, through Linkage Output of relay, the GN8020-E can be joined with the host of fire control, and cut-over fire control system immediacy. |
| |
| ■
Specification: |
| |
| Detecting
Theory |
Electrochemical type、PID type |
| Measurement
Range |
0~1/5/10/50/100/1000ppm |
| Accuracy |
±2%FS |
| Response
Time |
≤60s |
| Recovery
Time |
≤60s |
| Setting
Mode |
Magnet Pen |
| Alarm setting |
2-Stage alarm (default A1:25%F.S.A2:50%F.S,adjustable) |
| Alarm Mode |
Light Alarm (Green,Yellow,Red),2-stage alarm passive relay output contact (A1),contact capacity 1A 24VDC(Optional) |
| Explosion
Prevention Mark |
3/4"NPT/M20 |
| shell Material |
Al-Mg alloy / stainless steel |
| Explosion
Prevention Mark |
ExdⅡCT6 |
| Degree of protection |
IP66 |
| Working Temperature |
-40℃~+70℃ |
| Relative Humidity |
0~95%RH (Non-condensing) |
| Power Supply |
24VDC±8VDC |
| Maximum Power supply Consumption |
2.5W |
| Weight |
Approximately 1.5Kg |
| Shell color |
blue |
| Dimensions |
110mm*150mm*81mm(L*W*H) |
|
| |